A method of calculation of maximum arc energy was presented to assess the arcing fault damage. Arc model was improved for the calculation of arc energy in low-voltage power systems. The model was expressed as differential equation. Arc voltages in the model were determined with probability method based on a large number of three-phase arcing fault tests. The arc currents and arc energy were determined from differential equation. Two examples served to illustrate the calculation of arc energy. The examples show that the maximum arc energy depends primarily on arc voltage and bolted fault current. The method involves the stochastic characteristics of the fault arcs. It can be used easily to calculate the maximum arc energy in low-voltage power systems to minimize arcing fault damage

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.