Abstract

This paper proposes a novel and applicable approach to calculate the reactive power loss of converter transformer under dc bias. By using this proposed method, only general information of the converter transformer and the network is needed for the calculation within a certain dc current range. Specifically, a three-dimensional model of ±800 kV converter transformer model for simulation test is established by the finite element method. Through simulation test, the electromagnetic characteristics and reactive loss characteristics of converter transformer under dc bias can be obtained, and the relationship between the bias current and the reactive loss of ±800 kV converter transformer is quantified. Simulation results validate the feasibility of proposed algorithm.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.