Abstract

The transient recovery voltage (TRV) associated with power-transformer terminal faults is essential for correctly applying circuit breakers. Because presently used methods only allow for roughly estimating an equivalent single TRV ringing frequency, more accurate but inexpensive methods are needed. The novel method presented in this paper employs frequency response analysis (FRA) for measuring the transformer's complex short circuit impedance Z/sub X/. From that, the frequency spectrum of the TRV is approximated by the ratio of Z/sub X/ over the frequency square. Inverse fast Fourier transformation finally leads to the time domain signal. Comparing measured TRV signals from several field tests with the calculated ones prove this simple but effective method. Even multimode oscillations that cannot be reproduced by rough estimating tools are covered. It is concluded that the presented method provides a valuable tool for extracting inherent TRV parameters, either from routinely performed FRA measurements or from lightning impulse tests without significant additional costs.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.