Abstract
This paper reports an experience of using three building energy analysis programs- BLAST-3.0, DOE-2.1D and ESP version 7 release 2b. The programs are validated and their results compared for the subtropical climate of Hong Kong. Two occupied buildings have been studied to evaluate the programs; a ten-storey office building and a Polytechnic lecturer's office. The indoor conditions and the energy consumptions of the two buildings were measured. The predicted energy performance is compared with the measured energy consumption for the two buildings. Discrepancies between the simulated results and the measured performance, and likely problems in the application of these programs by practicing engineers, are discussed. The applicability of the three programs is further demonstrated by simulating the energy performance of a hypothetical test building, where the programs' predictions of building load imposed on the air conditioning plant are compared.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Building Services Engineering Research and Technology
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.