Abstract

With increasing penetration of rooftop PV systems on UK LV networks, it is becoming more likely that specific LV networks will experience unacceptable line congestion and voltage rises. In this study, we use Mixed Integer Quadratically Constrained Program (MIQCP) formulations to examine the possibility of eliminating these violations via aggregation and control of behind-the-meter (BTM) battery energy storage systems (BESSs), therefore delaying traditional reinforcement. By applying the formulations to 29 UK LV feeders, we examine the trends between the violation control capability of each method and a set of feeder topology metrics, to determine whether the suitability of networks to violation management strategies may be predicted from easy to obtain metrics, rather than extensive power flow modelling. It is found that instances in which BESSs may be reliably used to manage violations exist but are infrequent,

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.