Abstract

This paper investigates the potential inaccuracies associated with using a modal-domain model featuring a real and frequency-independent transformation matrix in simulating electromagnetic transients on power overhead lines equipped with underbuilt wires. Three transmission line configurations are examined: one without underbuilt wires, one with a single underbuilt wire, and another with two underbuilt wires. Comparisons between the simulated voltages computed using the modal-domain approach and a more accurate phase-domain model as a reference reveal that the modal-domain approach leads to inaccuracies in the simulated voltages. These inaccuracies intensify with an increase in the number of underbuilt wires and the soil resistivity. Differences of up to approximately 24 % in the peak values of the simulated voltages were observed, considering the transmission line geometry analyzed in this study. Based on these findings, it is recommended that for simulating transients in overhead lines with installed underbuilt wires, phase-domain models, such as the Universal Line Model, should be employed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.