Abstract
This paper presents a mathematical model to enable a more in-depth understanding of the combined heat and mass transfer processes of a counter-flow indirect evaporative cooler operating in semi-arid regions. A series of simulation was conducted to compare the performances between a single-purge and four-purge configurations. Furthermore, the effect of several parameters on the performance of the single-purge configuration was investigated under the baseline condition. The developed model was validated against experimental data from literature to within 2% discrepancy. Key results revealed that the single-purge configuration produced higher cooling capacity (around 20% higher), as well as higher dew-point effectiveness under the same operating conditions. A parametric study was also made on the single-purge configuration. The results revealed that lower product air temperature and higher dew-point effectiveness were achieved with longer channel length and larger purge ratio. However, the maximum cooling capacity approached its maximum with longer channel length and 35% purge ratio.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.