Abstract
This paper gives an analysis and design of a static synchronous compensator (STATCOM) using a series-connected hybrid multi-converter system. The hybrid multi-converter system consists of two GTO converters and an IGBT converter connected in series by transformers. The proposed STATCOM has advantages that the harmonic components of the output voltage/current would be less than a conventional configuration STATCOM composed of a 12-, 24-, or 48-pulse converter; the total switching losses would be less than a PWM STATCOM; and the response would be as rapid as a PWM STATCOM. One problem of the hybrid configuration STATCOM is that it tends to operate in an over-modulation range if a considerable compensating reference change occurs. To solve this problem, this paper also proposes a variable DC voltage control strategy, where the DC voltage is adaptively adjusted in accordance with the required reactive power. The validity of the proposed configuration STATCOM and control strategies are verified by simulation and experimental results.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.