Abstract

This paper presents tower surge response calculations on an actual transmission tower including ground wires and phase wires. A frequency-domain partial element equivalent circuit (PEEC) method is applied as a simulation tool. Insulator voltages calculated by the voltage difference of crossarms and phase wires are compared with experimental results collected from the literature. In addition, a transmission line (TL) model is adopted with the PEEC method to increase efficiency for transient surge calculation. The results calculated by the PEEC method with and without the TL model agree well with the experimental results not only for amplitudes but also for waveshapes.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.