Abstract

In this research work, dimensional analysis is used to determine the maximum withstand pollution severity level (represented as volume conductivity) of an insulator as a function of its profile parameters and applied voltage. To validate the derived dimensional equation, the maximum withstand severity (MWS) tests have been carried out on 15 different profiles of cap and pin insulators for 220 and 400 systems by salt fog test method. The developed dimensional equation is used as a predictive model to determine MWS of insulator by assuming corrective constants. By analysing the mean square error and root mean square error, the proposed model is found to be in agreement with experimental results.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.