Abstract

Installing magnetic shunts on the surfaces of tank and clamps of power transformer is able to reduce the eddy current losses and decrease the temperature rise effectively. Here, the three-dimensional transient finite element method and the magnetic thermal coupling method are used to calculate and analyse the effect of magnetic shunts with different structures. The non-linear magnetic property of both the transformer structural parts and the magnetic shunts are considered in the analysis. The lamination structure of the shunt is also considered, which is simulated by a thick plate with anisotropic magnetic property. A 334 MVA single-phase transformer is taken as an example in the analysis. The optimisation shunt structure is obtained. By comparing the L-shaped, the inverted L-shaped, and the U-shaped magnetic shunts for the clamps, it is proved that the U-shaped shunt is more effective in reducing the eddy current loss and temperature rise.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.