Abstract

This paper is focused on the analysis of the shielding properties of reinforced concrete under impinging high-altitude electromagnetic pulse. The reinforced concrete provides frequency-dependent shielding effectiveness mainly due to the embedded metallic grid rebars. For characterization of the concrete, three different configurations, i.e., concrete, rebar, and combined reinforced concrete, are analyzed in detail. In addition, the electromagnetic properties of concrete are quantitatively analyzed by its frequency dependence, moisture content, and material mixture ratio. According to the obtained results, as the rebar spacing decreases and the rebar diameter is increased, the transmission coefficient is gradually decreased. In particular, for reinforced concrete with built-in double layered rebar, it is possible to obtain a transmission coefficient approximately 40 dB less than that achieved by single rebar.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.