Abstract

Flow mal-distribution is defined as the non-uniform fluid flow distribution among the parallel channels having a common header. Flow mal-distribution is present in every header channel assembly. This mal-distribution has a significant effect on the performance of the heat exchanger by increasing the pressure drop and affecting the heat transfer characteristics. However, in designing a heat exchanger, a uniform flow distribution in each channel is assumed. The present work attempts to reduce the flow mal-distribution in a cross flow heat exchanger. A numerical analysis is done using a commercial code ANSYS FLUENT 3D and the results are validated experimentally. A parametric study is done by changing the size of the channels within the heat exchanger so as to reduce the flow mal-distribution. The effect of varying channel size on flow mal-distribution and pressure drop across the heat exchanger is studied and a geometry with reduced flow mal-distribution is found.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.