Abstract

In this study, a transcritical CO2 refrigeration system suitable for simultaneous pasteurization and chilling of milk in a dairy plant has been analysed. Performance comparison is made between CO2 systems with ejector (RCEP) and a conventional CO2 system without ejector (CRCP). Results are obtained for different arrangements of internal heat exchanger (IHX) in the flow line with a regenerative milk heat exchanger (HXD) for heat recovery. From the results, the optimum operating condition for maximum specific milk flow rate (m˙mw) is obtained. Results show that RCEP1, which uses an ejector and the internal heat exchanger in between the two gas coolers, offers around 13% better productivity compared to CRCP. Investigation on primary energy consumption of the transcritical CO2 system and systems employed in dairy plant conventionally for pasteurization show a substantial margin in energy savings for RCEP.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.