Abstract

The time of checking the registers of smart meters of accuracy class 0.2 S for indirect measurement of active electricity via instrument transformers, during the first, extraordinary or periodic control and verification has been significantly increased according to the latest Rules on meters of active electrical energy of accuracy class 0.2 S from December 23, 2016. This is especially pronounced when the meter is set to show the measured value of electrical energy in kWh on the secondary side of instrument transformers with the often used meter of active electrical energy of accuracy class 0.2 S, rated phase voltage 110 / √3 V and for the rated current 1 A. In that way, the total time as well as the costs of testing such meters has increased a lot. In addition, with electricity meters set in this way with a resolution of three decimal places and a unit in kWh, there is an additional error when reading the measured value of active electrical energy and especially when calculating the energy loss of active electrical energy. A more acceptable approach to setting such meters will be considered.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.