Abstract

In the Electrical Engineering Study Program, Udayana University, a Solar Power Plant was installed with a power of 26.4 kWp, a Wind Power Plant with a power of 5 kWp and a Diesel Power Plant with a capacity of 20 kVA. The size of harmonics in the electric power system is called Total Harmonic Distortion (THD). THDi's research results at DH Electrical Engineering Building of Udayana University before the operation of Distributed Generation (DG) were that R phase was 9.91%, S phase was 10.86%, and T phase was 9.85%. THDi value after the operation of Distributed Generation, R phase was 16.05%, S phase was 17.53%, and T phase was 15.70%. THDi value with LC filter, R phase was 4.0%, S phase was 5.52% and T phase was 3.97%. THDv value before the operation of Distributed Generation, R phase was 0.08%, S phase was 0.48% and T phase was 0.47%. THDv value after the operation of Distributed Generation, R phase was 0.24%, S phase was 0.44% and T phase was 0.49%. THDv value with LC filter, R phase was 0.01%, S phase was 0.01% and T phase was 0.02%. The results of the research showed that losses before the operation of Distributed Generation were 115.53 Watts and the value of losses after the operation of Distributed Generation had increased to 130.07 Watts.

Highlights

  • a Solar Power Plant was installed with a power of 26.4 kWp

  • The results of the research showed that losses before the operation

  • the value of losses after the operation of Distributed Generation had increased to 130.07 Watts

Read more

Summary

PENDAHULUAN

Di program studi Teknik Elektro Universitas Udayana terpasang PLTS, PLTB dan. PLTD, dengan daya terpasang dari PLTS sebesar 26,4 kWp, PLTB sebesar 5 kWp dan sebuah PLTD yang memiliki kapasitas. Media penyimpanan energi listrik yaitu baterai dengan kapasitas 192 kVAh [1]. PLTS membangkitkan energi listrik searah (DC), maka dipasanglah peralatan elektronika daya yaitu inverter yang bertujuan untuk merubah energi listrik searah (DC) menjadi energi listrik bolak balik (AC). PLTB membangkitkan energi listrik AC dan dikonversikan ke DC menggunakan rectifier untuk mengisi daya baterai. DC dari baterai dikonversikan ke AC oleh inverter untuk melayani beban yang terpasang. Peralatan elektronika daya seperti inverter dan rectifier merupakan penyebab timbulnya distorsi harmonisa. Pada penelitian ini akan membandingkan distorsi harmonisa sebelum beroperasinya DG, setelah beroperasinya DG dan setelah dipasang LC filter dengan menggunakan perangkat lunak. Simulink serta membandingkan nilai losses sebelum dan setelah beroperasinya DG

KAJIAN PUSTAKA
Filter Pasif
METODE PENELITIAN
Hasil Pengukuran Beban di Gedung DH Teknik Elektro Universitas Udayana
Analisis THD Berdasarkan IEEE 5192014
KESIMPULAN
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.