Abstract

The results of full-scale tests of smoke interface height in atrium fires with different make-up air velocities and opening arrangements, including asymmetric openings and openings that resulted in rotational air flows, are presented in this paper. The non-symmetric opening arrangements included openings on 3 sides of the atrium, 2 adjacent sides and 1 side. Make-up air velocities of 1, 1.5 and 2 m/s and fire sizes of 1, 2 and 5-MW were considered. Temperature was recorded along the height of the atrium by setting up thermocouple trees, and the temperatures measurements were used to determine the experimental smoke interface height using the N-percentage method. Predicted smoke layer height from the atrium plume correlation is compared with the full-scale test data. The results show that even a 1 m/s make-up air velocity can cause a significant decrease in the smoke interface height in the case of an asymmetric opening arrangement and rotational air flows in the atrium. The full-scale test data are used to propose a correlation to calculate the reduction of smoke interface height for the design of smoke exhaust systems in atria.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.