Abstract
R-410A distribution was experimentally studied for a parallel flow evaporator having two row/four pass configuration. The evaporator has inlet, intermediate and row-crossing headers. Tests were conducted for the mass flux from 70 to 130 kg/m2s with the quality at the inlet of 0.2 and exit superheat 5 °C. Significant heat transfer degradation (13–40 %) was realized for the two row/four pass configuration due to flow mal-distribution. Of the three insert hole sizes, 4.0 mm hole yielded the least heat transfer degradation followed by 6.0 and 2.0 mm holes. At the inlet header, more liquid flowed into upstream channels. At the intermediate headers, more liquid was supplied into downstream channels. Similar flow distribution was obtained before and after the row crossing header. Header pressure drops were obtained by subtracting the flat tube pressure drops and other minor pressure drops from measured pressure drops.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.