Abstract

Design of plugs for abandonment of boreholes and shafts may be governed by the bond strength between the plug and host rock. This paper presents the results of push-out tests on cement grout plugs in salt. Two types of expandable cement grouts have been tested. The average interface shear strengths ranged from 2 to 12 MPa (290 to 1740 psi). Peak shear stresses at failure, assuming an elastic stress distribution along the interface, were up to eight times higher. Standard deviations commonly reached 20%. Dissolution along the interface was observed, and may have been enhanced by clay inclusions in the salt. This dissolution appears to have reduced bond strengths. Application of the results to the design of plugs for larger openings (for example, shafts, drifts, or boreholes) is discussed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.