Abstract

This paper describes an accurate fault location algorithm based on sequence current distribution meters for a double-circuit transmission system. The proposed method uses the voltage and current collected at only the local end of a single-circuit. This method is virtually independent of the fault resistance and the mutual coupling effect caused by the zero-sequence current of the adjacent parallel circuit and insensitive to the variation of source impedance. The fault distance is determined by solving the forth-order KVL (Kirchhoff's voltage law) based distance equation. The zero-sequence current of adjacent circuit is estimated by using a zero-sequence current distribution factor and the zero-sequence current of the self-circuit. Thousands of fault simulations by EMTP have proved the accuracy and effectiveness of the proposed algorithm.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.