Abstract

In order to get the airside heat transfer and pressure drop correlations of corrugated fin-and-tube heat exchangers with hydrophilic coating under wet conditions,experiments on 7 heat exchangers under 23 working conditions are done.The experimental data are used to develop the correlations for heat transfer and pressure drop with the multiple linear regression technique.The proposed heat transfer correlation has a mean deviation of 6.5%from experimental data and can predict 90.3%of the experimental data within the deviation limit of±15%while the pressure drop correlation has a mean deviation of 9.1%and can correlate 79.2%of the test data within the deviation limit of±15%.The accuracy of the new correlations is better than that of the existing correlations.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.