Abstract

Experimental studies on the air-side heat transfer and pressure drop characteristics for 16 types offset strip fins and flat tube heat exchangers were performed. Parameters including fin space s, fin height h, fin thickness t, fin length l and flow length d, a series of tests were conducted in region of air-side Reynolds number 500–7500, at a constant tube-side water flow rate of 2.5 m 3/h. The air-side thermal performance data were analyzed using the effectiveness-NTU method. The heat transfer coefficients and pressure drop data with different fin space s, fin height h, and fin length l were reported in terms of frontal air velocity. The general correlations for Colburn j-factor and Fanning fraction f-factor were derived by regression analysis and F significance test. The correlations for j and f factors can predict 95% and 90% of the experimental data within ± 10%. And the average deviations of predictive data for the j and f factors are 0.2% and 1.2%, mean deviations are 4.2% and 5.3%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.