Abstract

This paper presents a method for accurate fault localisation of DC-side faults in Voltage Source Converter (VSC) based Multi-Terminal Direct Current (MTDC) networks utilising optically-multiplexed DC current measurements sampled at 5 kHz, off-line continuous wavelet transform and machine learning approach. The technical feasibility of optically-based DC current measurements is evaluated through laboratory experiments using commercially available equipment. Simulation-based analysis through Matlab/Simulink® has been adopted to test the proposed fault location algorithm under different fault types and locations along a DC grid. Results revealed that the proposed fault location scheme can accurately calculate the location of a fault and successfully identify its type. The scheme has been also found to be effective for highly resistive fault with resistances of up to 500Ω. Further sensitivity analysis revealed that the proposed scheme is relatively robust to additive noise and synchronisation errors.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.