Abstract

The voltage received by each customer connected to a power distribution line with local controllers (inverters) is regulated to be within a desired margin through a class of slope-restricted controllers, known conventionally as droop controllers. We adapt the design of the droop controllers according to the known bounds of the net power consumption of each customer in each observation time window. A sufficient condition for voltage regulation is provided for each time window, which guides the design of the droop controllers, depending on the properties of the distribution line (line impedances) and the upper bound of all the customers’ power consumption during each time window. The resulting adaptive scheme is verified on a benchmark model of a European low-voltage network by the CIGRE task force.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.