Abstract

AbstractThe design and development of an adaptive hybrid predictive controller for the optimization of a real combined cycle power plant (CCPP) are presented. The real plant is modeled as a hybrid system, i.e. logical conditions and dynamic behavior are used in one single modeling framework. Start modes, minimum up/down times and other logical features are represented using mixed integer equations, and dynamic behavior is represented using special linear models: adaptive fuzzy models. This approach allows the tackling of special non‐linear characteristics, such as ambient temperature dependence on electrical power production (combined cycle) and gas exhaust temperature (gas turbine) properly to fit into a mixed integer dynamic (MLD) model. After defining the MLD model, an adaptive predictive control strategy is developed in order to economically optimize the operation of a real CCPP of the Central Interconnected System in Chile. The economic results obtained by simulation tests provide a 3% fuel consumption saving compared to conventional strategies at regulatory level. Copyright © 2007 John Wiley & Sons, Ltd.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.