Abstract

FACTS devices are presently used to improve the power transfer capability of a transmission line and voltage stability of a power system network. Shunt injected current (Ish) by the Static Var Compensators (SVC) causes underreach or overreach of distance relay when not considered during relay calibration of protection system. This paper presents an adaptive relay setting procedure in the presence of a SVC connected at the midpoint of a transmission line. The remote terminal unit RTU is connected to the SVC terminal via a current transformer (CT) measures the injected shunt current when the SVC is the switch in or out of the network and transferred the measured value to the local station via fiber optic. The PSCAD/ EMTDC software is used to model an adaptive relay that implements the conventional and adaptive relay system settings. The proposed scheme presents a hybrid distance protection system whose setting is based on the prevailing SVC switching conditions; the relay system was implemented using mho characteristics relay. The results obtained show that the proposed scheme has a high accurate setting.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.