It mainly depends on the anti-aging performance whether heat-shrinkable tubes for busbar can maintain excellent electrical and mechanical properties during long term operation. In this paper, the samples were applied to the switchgear busbar of 10 kV and 35 kV in substations of Tianjin Power System. Their operating time is 0, 1, 2, 9 years and 0, 4, 6 years respectively. Tensile strength (breaking strength, elongation at break), dielectric permittivity, dielectric loss tangent, AC impedance and breakdown characteristics under AC voltage are tested. The result shows that the tensile strength decreases while dielectric permittivity and loss tangent increase with the operating time. The decline of breakdown strength and AC impedance indicates that insulation capability is reduced by long time natural aging.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.