Abstract

The increasing application of floor heating technology promotes the development of floor radiant cooling technology (abbreviated as FRC technology). Many office buildings in northern China try to use FRC technology to cool in summer, but thermal comfort is the key problem restricting the promotion of this technology. The thermal comfort problems of an office room with floor radiant cooling were studied in this paper by the methods of numerical simulation, control variable, and data fitting, and the experimental results were verified in multiple ways. It was found that, for an office room using floor radiant cooling, the effect of the floor surface temperature on thermal comfort was about 16%, while the effect of indoor air temperature was about 84%, and relative humidity had little effect on thermal comfort. A simplified thermal comfort calculation model was proposed, which could be used as an indicator to adjust the floor surface and indoor air temperature, or could be used to calculate the PMV-PPD value. The findings have guiding significance for the design and control of FRC technology.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.