Abstract

This paper presents a simple method to minimize lightning surges entering an uprated or compact substation. A severe lightning stress is caused by a backflashover in close proximity to the substation. Feasibility of uprating is based on the surge arrester technology available at present. However, some aspects of line design offer opportunities in reducing frequency and severity of lightning surges imposed on the substation. The tower surge response adds an inductive 'overshoot' only during the front of the stroke which reduces considerably during the tail. If backflashover does not occur before reflections from adjacent towers arrive, it is unlikely to occur at all. Use of guys and underbuilt ground wires in the limiting distance will produce reflections with larger magnitude and reduce the effective surge impedance of the tower. This would not only reduce backflashover frequency but will also minimize crest and duration of surges entering the substation.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.