Abstract
The feedforward schemes of the voltage at point of common coupling (PCC) have been widely used in grid-connected inverters to reject the current harmonics caused by the grid voltage distortion. However, in weak grid, the PCC-voltage feedforward tends to destabilize the grid-connected inverters due to the effect of time delay. In this article, this stability issue is explicitly elaborated by the impedance-based stability criterion and then addressed with an improved feedforward scheme, which uses the grid voltage instead of the PCC voltage as the feedforward variable. Considering that it is hard to sense the real grid voltage directly, a method to extract the grid voltage from the sensed PCC voltage is put forward to implement the proposed feedforward scheme. By carefully arranging the sampling instants according to the duty cycle, a dual sampling mode is adopted to ensure an accurate extraction of the grid voltage. Finally, simulations and experiments are performed on a 6-kW single-phase grid-connected inverter, which confirm that the proposed grid-voltage feedforward achieves superior harmonic rejection ability and strong stability under weak grid condition.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.