Abstract

This paper presents an advanced technique for the differential protection of single core phase shifting transformers. The proposed technique is based on sensing electrical signals without sensing tap position. Only terminals currents are sensed by using two current transformers (CTs) per phase unlike other methods that need more CTs. Other methods use at least four transducers per phase and, in addition, sense the tap changer position, which increases the cost of the protection system. The proposed technique is based on the analysis of magnetically coupled and metallically connected circuits. The excitation winding currents are calculated to represent input currents to the differential protection relay. Tap changer position is estimated according to the phase shift between sources currents. The technique is checked for various types of shunt faults inside and outside the protection zone. The results prove the relay sensitivity and stability for internal and external faults, respectively. The effects of inrush current, series winding and CTs saturation are taken into consideration.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.