Abstract

In the distribution system including distributed generators, it is difficult to meet the requirements of selectivity and sensitivity for traditional current protection. Currently, inverter-based distributed generators (IBDG) are widely used in distribution systems. The transient process of IBDG is rapid, and its transient characteristics are influenced by the control strategy. The controlled current source equivalent model of IBDG with positive-sequence P-Q control is put forward. After analyzing the fault characteristics, the protection scheme using negative sequence current is proposed, which can be used in the distribution systems including IBDG under positive-sequence P-Q control. The simulation results on a 10kV distribution system have verified the correctness of faults characteristics and the effectiveness of protection scheme.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.