Abstract
A parametric natural fire model is presented, which is derived on the basis of simulations with heat balance models for realistic natural design fires, taking into account the boundary conditions of typical compartments in residential and office buildings. These so-called iBMB parametric fire curves are formulated with the help of simplified empirical equations which can easily be used for structural fire design as part of a performance-based natural fire design concept. The iBMB parametric fire curves are checked and validated by comparison with results of different heat balance models and with published fire tests from different fire research laboratories. In addition, a natural fire test in a test room with ordinary office room furnishings has been performed which supports the parametric natural fire model presented here. The application of the iBMB parametric fire curves is demonstrated by means of an example.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.