Abstract
AbstractDetermining the harmonic contribution of each harmonic source is conducive to improving the harmonic management of the power system. The main problem with harmonic contribution calculation is determining the equivalent system harmonic impedance. The previous harmonic impedance calculation method can only calculate the impedance value when the harmonic fluctuation is significant, and the calculation fails when the harmonic fluctuation is small. Therefore, a new method called difference recurrence estimation is proposed to construct the objective function from impedance parameters. The advantages of the proposed method are low data requirement, high estimation accuracy, and excellent tracking performance. An improved genetic algorithm (GA) is presented by integrating an adaptive crossover operator and population intervention into the standard GA to improve the global searching impedance parameter ability. Based on these parameters, harmonic impedance and harmonic contribution are calculated accurately. The superiority of the proposed model is verified through simulation and field cases.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.