Due to current sensor errors, tolerance of power switching devices, and asymmetry of PWM gating driving pulses, grid-connected inverters without isolation transformer usually have certain amount of dc components injected to the ac grid. Many efforts, such as using a blocking capacitor, a current dc component feedback control, and a voltage dc component feedback control have been introduced to try to suppress the dc injection to the grid. This paper proposes a novel control strategy of suppressing dc current injection to the grid for a three-phase inverter by accurately sensing the dc component of line voltages of three-phase inverter and adding a dc component control loop. A dc suppression control scheme is presented, and the suppression performance of the proposed dc rejection method is evaluated and compared with the traditional method. Finally, the control scheme is verified on a 20-kW three-phase grid-connected inverter.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.