Abstract

This paper presents a passive islanding detection method for inverter-based distributed generation based on empirical mode decomposition (EMD) technique. The voltage of point of common coupling (PCC) is measured and its intrinsic mode functions (IMFs) are obtained using EMD. The first IMF component of PCC per unit voltage is the parameter used for islanding detection. Performance of the proposed method is evaluated for single-DG and multi-DG cases. Simulation results performed in MATLAB/SIMULINK environment show that the islanding can be detected in less than two cycles, even for zero power mismatch. Moreover, the proposed method functions properly for various configurations of multi-DG systems, DGs switching events, various loadings of DGs and different DG interface controls.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.