Abstract

An analytical model is developed for quantifying the fire smoke back-layering length in a tunnel with a combination of longitudinal ventilation and point extraction ventilation in the roof. The distance of smoke vent to fire source is incorporated as well as mass flow rate during the whole smoke flow process according to the mass conservation principle. The model input quantities are the heat release rate of the fire source, the longitudinal velocity, the exhaust velocity, the width and the height of the tunnel, the distance of the smoke vent to the fire source and the area of the smoke vent. The quality of the model predictions is illustrated for a range of experimental conditions. After that, extensive model predictions on the back-layering length are presented to show its trends by varying the velocity of the longitudinal ventilation, the exhaust velocity and the position of the smoke vent in the roof. Discussions are given at last. It is highlighted that shortening the distance between the smoke vent and the fire source benefits shortening the back-layering length, and this phenomenon is more pronounced for higher exhaust velocity.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.