Abstract
Variable impedance apparatus such as a static VAr compensator (SVC) and a variable series capacitor (VSC) can improve the steady-state stability of a power system if they are located appropriately. The present paper proposes an index for identifying the location of SVC and VSC in large scale power systems for effective damping. The index is called LIED (location index for effective damping) by the authors. Since LIED can be computed quickly for large scale power systems which have more than two hundred generators without conducting a number of digital simulations and eigenvalue analyses, it is valuable for the system planner who needs to identify the effective location of SVC and VSC. The proposed index is applied to the New England test system and its validity is demonstrated through digital simulations. >
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.