Abstract

To clarify the indoor climate in Japanese college classrooms, an air-conditioned, mechanically ventilated classroom of a university was surveyed. Temperatures, humidity and carbon dioxide (CO2) concentration in winter and summer were measured before, during and after lessons. The airtightness of the room and the airflow rate of the ventilation system were also measured. In winter, at an outdoor air temperature around 0 °C and with the thermostat temperature of the air conditioners set to 30 °C, the vertical difference in room air temperature exceeded 10 °C. The relative humidity (RH) was about 30% during lesson hours. After half an hour of occupancy, the CO2 concentration exceeded 1500 ppm in the respiration zone. It subsequently reached 2500 ppm, as measured within the respiration zone at half room height, after a continued 1.5 hours of occupancy. No special thermal or humidity problems were found in the summer survey. However, the CO2 level was very close to that of winter. The CO2 concentration decays indicated that the air change rate was 0.82 to 0.87 ac/h, which satisfied the Japanese criterion of 0.3 ac/h for the prevention of formaldehyde, yet it was far below the national criterion of 4.4 ac/h for college classrooms.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.