Abstract

In the absence of empirical outdoor thermal comfort studies it has been widely assumed that indoor thermal comfort theory generalises to outdoor settings without modification. Many indoor models were developed to describe thermal discomfort, not stress, therefore their relevance to conditions that vary greatly from neutrality, as many outdoor climatic conditions do, has not been critically validated in the field to date. The thermal comfort of 1018 subjects in outdoor and semi-outdoor locations in subtropical Sydney was investigated by a questionnaire and a comprehensive package of micro-meteorological instruments. The thermal neutrality in terms of the thermal comfort index OUT_ SET ∗ of 26.2°C was significantly higher than the indoor SET ∗ counterpart of 24°C (ASHRAE Trans. 92 (1986) 709).

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.