Abstract

With steadily increasing wind turbine penetration, regulatory standards for grid interconnection have evolved to require that wind generation systems ride-through disturbances such as faults and support the grid during such events. Conventional modifications to the doubly fed induction generation (DFIG) architecture for providing ride-through result in compromised control of the turbine shaft and grid current during fault events. A DFIG architecture in which the grid side converter is connected in series as opposed to parallel with the grid connection has shown improved low voltage ride through but poor power processing capabilities. In this paper, a unified DFIG wind turbine architecture which employs a parallel grid side rectifier and series grid side converter is presented. The combination of these two converters enables unencumbered power processing and robust voltage disturbance ride through. A dynamic model and control structure for this architecture is developed. The operation of the system is illustrated using computer simulations.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.