Abstract

A new fault-location algorithm for series-compensated double-circuit transmission lines utilizing two-terminal unsynchronized voltage and current measurements is presented in this paper. The mutual coupling between the parallel lines in the zero-sequence network is fully considered. The distributed parameter line model is adopted to fully take into account the shunt capacitance of the line. By formulating voltages and currents at the fault point in terms of the unknown fault location, boundary conditions under different fault types are used to derive the fault location. Two subroutines assuming the fault occurs on the left or right side of the series compensator are developed and the principle to identify the correct fault-location estimate is described. Matlab SimPowerSystems is employed to generate cases under diverse fault conditions for validating the proposed fault-ocation algorithm. Evaluation studies have shown that the proposed algorithm has achieved quite accurate results.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.