Abstract
The hot-wall heat exchanger (HWHE) has been widely used in thermal engineering fields such as ceiling radiant heating/cooling, refrigerator condenser, solar heat collection, and high-temperature heat recovery. However, the numerical simulation normally used for heat transfer prediction in HWHE is usually not as convenient as the analytic solutions in engineering applications. In this paper, a new heat transfer mathematical model of HWHE-based on analytic solutions was developed, which could be much faster to obtain the heat transfer properties of HWHE. The proposed model was validated under four conditions with literature values, which showed that the deviations of heat flux are 2.53%, 0.99%, 2.12%, and 1.96%, indicating its accuracy is satisfied. The model was then used to analyze the thermal property of HWHE. The results show the thermal resistance caused by panel with heat convection and conduction accounts for 96.54% of HWHE thermal resistance, and the thermal resistance caused by heat convection on the surface of panel is 74.43%. The analyzation results also show that adding aluminum foil around pipes could decrease HWHE thermal resistance by 5.11%. Besides, the influence of pipe diameters, pipe distance, pipe heat conductivity, side wall heat conductivity, and convective heat transfer coefficient on the heat transfer performance of HWHE was analyzed. The research in this paper can be used for fast prediction and optimization of heat transfer in HWHE.
Highlights
The hot-wall heat exchanger (HWHE) has been widely used in thermal engineering fields such as ceiling radiant heating/cooling, refrigerator condenser, solar heat collection, and high-temperature heat recovery
The study proposed in this paper developed a mathematical model based on analytic solutions aimed at improving the simulation accuracy and facilitating the thermal prediction of HWHE heat transfer performance
It is found that the deviations of heat flux on the heat exchanger are 2.53%, 0.99%, 2.12%, and 1.96%, proving the accuracy of the proposed model
Summary
Beijing Key Lab of Heating, Gas Supply, Ventilating and Air Conditioning Engineering, School of Environment and Energy Engineering, Beijing University of Civil Engineering and Architecture, Beijing.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.