Abstract

Specially designed arresters are used in the American Electric Power 765-kV station insulation coordination as a first line of defense against overvoltage. The arresters have the ability to withstand sustained and dynamic overvoltages in excess of their rating. They also have the ability to discharge repetitively. Use of these arresters permitted 1800-kV BIL ratings for transformers, reactors, and circuit breakers. A performance criterion for bus flashover was established in terms of probability. New methods were used to test station insulator withstand and contamination performance.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.