Abstract

In this study, comparative analysis on the back-layer phenomena in the tunnel-fire driven flow is performed using numerical simulation with LES and RANS. FDS(Fire Dynamics Simulator) code is employed to calculate the fire-driven turbulent flow for LES and Smartfire code is used for RANS. Hwang and Wargo's data of scaling tunnel fire experiment are employed to compare with the present numerical simulation. The modeled tunnel is 5.4m(L) × 0.4m(W) × 0.3m(H). Heat Release Rate (HRR) of fire is 3.3㎾ and ventilation-velocity is 0.33m/s in the main stream. The various grid-distributions are systematically tested with FDS code to analyze the effects of grid size. The LES method with FDS provides an improved back-layer flow behavior in comparison with the RANS (k-ε) method by Smartfire. The FDS solvers, however, overpredict the velocity in the center region of flow which is caused by the defects in the tunnel-entrance turbulence strength and in the near-wall turbulent flow in FDS code.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.