Abstract
Abstract: In the field of shipbuilding and marine, electrical power system is that each of the distributed bus bars is connected electrically. In this way, it would be appropriate to recognize as grid-connecting rather than the redundant bus. Short-circuit capacity of the electric power system will be increased proportionally which is due to the addition of the bus. The increase of short-circuit capacity needs high initial cost associated with equipment and can generate the blackout when the equipment with a physically connected to the bus occurs the electric failure. In order to solve these problems, marine electrical power system in which current limiting reactor has been applied is classified according to the network topology, bus network, star network and ring network. And short circuit analysis for each network is performed by the fault types. The results are pre-sented pros and cons compared to each other. Keywords: Electrical power system, Current limiting reactor, Blackout, Bus Topology
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Journal of the Korean Society of Marine Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.