Abstract

This study represents the effective fire and smoke control in the case of fire in deep underground tunnels, even if the exhaust system can be calculated, the optimal smoke capacity can be determined by establishing technical standards for the transverse ventilation system focusing on the design as a basis for deriving the parameters for utilization. Numerical analyses were performed using the FDS program as a function of the unsteady flow in a deep underground tunnel fire. The analysis results were calculated within 250 m smoke using an inside wind velocity of 0m/s when the capacity of smoke was exhausted, 80 m 3 /s, whereas in case of an internal wind velocity of 3m/s, the

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.