Abstract

This study reviewed the capturing performance of a canopy hood used in some melting processes of a casting manufacturing factory through a site survey. In addition, this study compared and evaluated the flow field and pressure field for the plans to enhance the hazardous air pollutants collection capacity by using CFD model. The case-2(flange attached + double hood) can be improved in terms of collection performance, but is expected to increase in hood static pressure by about 70% more than the existing structure, so it was shown that its site applicability is not good. It is judged that the shape of case-3(flange attached + double cone attached) is most suitable to improve the suction efficiency. This is because a double cone is installed at the center of the opening to concentrate the flow rate on the edge of the hood and control the hume rising to the center of the hood without a static pressure rise via the slope of the cone.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.