Abstract
Local energy markets represent a separate distribution system with several sources of distributed generation and with its own network-independent operator. The cost of electricity in local systems depends on many criteria. They include the consumption of primary fuel for diesel generators, which depend on their capacity. Equal distribution of power on generators running in parallel leads to an increase in primary fuel consumption. An algorithm for optimizing fuel consumption, which calculates the power distribution of generators connected in parallel, has been developed. These capacities correspond to the minimum value of fuel consumption. The system using three diesel generators and the option of replacing one generator with a solar electric installation was considered. The use of the optimal algorithm allows for reducing the price by an average of 9 to 20% if compared to the uniform distribution. The introduction of a photovoltaic system with a rechargeable battery allowed to increase energy efficiency and reduce the price due to lower running costs of the solar installation. References 10, figures 3, tables 1.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.